ETS-Lindgren's LTC Series of filters are ideal for applications including communication lines entering or leaving shielded rooms, computer rooms, communication terminal rooms, and Sensitive Compartmental Information Facilities (SCIF). 

The LTC-X640 series filters have multiple circuits to handle 2, 4, 6, 8, 10 or 12 wires, and are designed for stand-alone, individual mounting. The LTC-X640 series filters may be supplied with an optional threaded conduit pipe for penetration of a shielded enclosure.

Key Product Information


Specifications Select a tab below for more information



​Passband Impedance
​Passband Loss
​Stopband Insertion Loss
​Maximum Current
​Maximum Voltage
​600 (L-L), 300 (L-G)
​1.0 dB Maximum; 0 to 5 kHz
​100 dB Minimum @ 14 kHz to 18 GHz
​0.5
125

NOTE: For Installation on shield, filters can be ordered with penetration kit. Add "/PEN" to model numbers

Model
Number of Lines
​Width
​​​LTC-2640-600Z
2
​7.62 cm (3.0 in)
​LTC-4640-600Z
4
15.24 cm (6.0 in)
​​LTC-6640-600Z
​6
​30.48 cm (12 in)
​​LTC-8640-600Z
​8
​30.48 cm (12 in)
​​LTC-10640-600Z
​10
​45.72 cm (18 in)
​​LTC-12640-600Z
12​​45.72 cm (18 in)

NOTE: For Installation on shield, filters can be ordered with penetration kit. Add "/PEN" to model numbers


View BIM Models of our Product Options Below:

 

 

Key Features


  • For 2 to 12 Line LTC Filters
  • Signal, Sensor & Voice Communication
  • Data Communication
  • Control Line

Literature and Videos


Date Last Updated: Wednesday, October 11, 2017